Communication
3.2 Communication services
CPU 31xC and CPU 31x, Technical Data
Manual, 01/2006 Edition, A5E00105475-06
3-25
How to use open IE communication
To allow data to be exchanged with other communication partners, STEP 7 provides the
following FBs and UDTs under "Communication Blocks" in the "Standard Library":
Connection oriented protocols: TCP-native, ISO-on-TCP
FB 63 "TSEND" for sending data
FB 64 "TRCV" for receiving data
FB 65 "TCON", for connecting
FB 66 "TDISCON", for disconnecting
UDT 65 "TCON_PAR" with the data structure for the configuration of the connection
Connectionless protocol: UDP
FB 67 "TUSEND" for sending data
FB 68 "TURCV" for receiving data
FB 65 "TCON" for establishing the local communication access point
FB 66 "TDISCON" for resolving the local communication access point
UDT 65 "TCON_PAR" with the data structure for configuring the local communication
access point
UDT 66 "TCON_ADR" with the data structure of the address parameters of the remote
partner
Data blocks for the configuration of the connection
Data blocks for configuring TCP native and ISO-on-TCP connections.
To configure your connection, you need to create a DB that contains the data structure of
UDT 65 "TCON_PAR." This data structure contains all parameters you need to establish
the connection. You need to create such a data structure for each connection, and you
can also organize it in a global DB.
Connection parameter CONNECT of FB 65 "TCON" reports the address of the
corresponding connection description to the user program (for example,
P#DB100.DBX0.0 byte 64).
Data blocks for the configuration the local UDP communication access point
To assign parameters for the local communication access point, create a DB containing
the data structure from the UDT 65 "TCON_PAR" This data structure contains the
required parameters you need to establish the connection between the user program and
the communication level of the operating system
The CONNECT parameter of the FB 65 "TCON" contains a reference to the address of
the corresponding connection description (e.g. P#DB100.DBX0.0 Byte 64).
Note
Setting up the connection description (UDT 65)
The interface to be used for for communication (for example B#16#03: Communication
via the integrated IE interface for the CPU 319-3 PN/DP) has to be entered in the UDT 65
"TCON_PAR" in the parameter "local_device_id".

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals