Communication
3.2 Communication services
CPU 31xC and CPU 31x, Technical Data
3-26 Manual, 01/2006 Edition, A5E00105475-06
Establishing a connection for communication
Use with TCP native and ISO on TOP
Both communication partners call FB 65 "TCON" to establish the connection. In your
connection configuration, you define which communication partner activates the
connection, and which communication partner responds to the request with a passive
connection. To determine the number of possible connections, refer to your CPU's
technical specifications.
The CPU automatically monitors and holds the active connection.
If the connection is broken, for example by line interruption or by the remote
communication partner, the active partner tries to reestablish the connection. You do not
have to call FB 65 "TCON" again.
FB 66 "TDISCON" disconnects the CPU from a communication partner, as does STOP
mode. To reestablish the connection to have to call FB65 "TCON" again.
Use with UDP
Both communication partners call FB 65 "TCON" to set up their local communication
access point. This establishes a connection between the user program and operating
system's communication level No connection is established to the remote partner.
The local access point is used to send and receive UDP telegrams.
Disconnecting
Use with TCP native and ISO on TCP
FB 66 "TDISCON" disconnects the communication connection between CPU and
communication partner.
Use with UDP
FB 66 "TDISCON" disconnects the local communication access point, i.e., the connection
between user program and communication level of operating system is interrupted.
Options for interrupting the communication connection
Events causing interruptions of communication:
You program the cancellation of connections at FB 66 "TDISCON."
The CPU goes from RUN to STOP.
At POWER OFF / POWER ON
Reference
For detailed information on the blocks described earlier, refer to the
STEP 7 Online Help.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals