EasyManua.ls Logo

Siemens Simatic S7-400 - UDT756 Uatimestamp; FB236 Ua_Writelist; Function and Call Interface - Ua_Writelist

Siemens Simatic S7-400
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programming the OPC UA client blocks
5.9 FB236 UA_WriteList
CP 443-1 OPC UA
Operating Instructions, 01/2017, C79000-G8976-C427-02
101
Table 5- 14 Coding of the memory area
Hexadecimal code
Area
Description
b#16#80
P
Memory area of the I/O
b#16#81 E Memory area of the inputs
b#16#82
A
Memory area of the outputs
b#16#83 M Memory area of the bit memory
b#16#84
DB
Data block
5.8.6
UDT756 UATimeStamp
UATimeStamp
Contains the time stamps of the elements of the data area in milliseconds. UATimeStamp
supplies the block parameter "TimeStamps".
Table 5- 15 Parameters of UDT UATimeStamp
Parameter
S7 data type
Range of values
Meaning
TimestampL WORD see below Least significant word (bits 0..15)
TimestampH
WORD
see below
Most significant word (bits 16..31)
Range of values of the entire double word:
TOD#0:0:0.0 .. TOD#23:59:59.999 (0 .. 86 399 999 milliseconds)
5.9
FB236 UA_WriteList
5.9.1
Function and call interface - UA_WriteList
Function of the block
With the block you write data to the connected UA server.
You program the attributes to be written in a UDT "UANodeAdditionalInfo" that is referenced
by the input parameter "NodeAddInfos".
The handles required at the input parameter "NodeHdls" are read from array of the output
parameter "NodeHdls" of the "UA_NodeGetHandleList" block.
The number of nodeIDs at the input parameter "NodeIDCount" is always 1 so you need to
call the block separately for each target node.

Table of Contents

Other manuals for Siemens Simatic S7-400

Related product manuals