Configuration and operation
4.8 Configuration of the CP in STEP 7 Professional
CP 443-1 OPC UA
64 Operating Instructions, 01/2017, C79000-G8976-C427-02
S7 communication
Certificate manager
Via the local certificate manager, you can import and export certificates for the CP.
You will find help on the certificate manager in the STEP 7 information system ate
following location:
"Editing devices and networks >Configuring devices and networks >Configure networks
> Industrial Ethernet Security > Configuring security > General > Managing certificates"
4.8.7
Security > "Time-of-day synchronization"
Synchronization method
Note
Recommendation for setting the time
If the infrastructure of your project allows, synchronization with a external clock at intervals of
approximately 10 seconds is recommended. This achieves as small a deviation as possible
between the internal time and the absolute time.
if the security functions are enabled, the CP supports the following methods of time-of-day
synchronization:
SIMATIC mode
The SIMATIC mode cannot be configured.
If you leave the time-of-day synchronization via NTP disabled, the SIMATIC mode is
enabled automatically on the CP. In this case, the CP can only adopt the time of day from
the station.
Note that with the CP as OPC UA server when using the SIMATIC mode the time is not
displayed as UTC but as the local time of the station.
NTP
If the option is enabled and the Security functions disabled, the CP synchronizes its time
of day via NTP.
When NTP is enabled, the CP as OPC UA server displays the time of day in the UTC
format.
You configure the synchronization method, the local time zone of the station, the
synchronization interval and the addresses of the NTP servers.
NTP (secure)
If the Security functions are enabled, the time of day can be synchronized using
NTP (secure),
The secure method NTP (secure) uses authentication with symmetrical keys according to
the hash algorithms MD5 or SHA-1.

Table of Contents

Other manuals for Siemens Simatic S7-400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simatic S7-400 and is the answer not in the manual?

Siemens Simatic S7-400 Specifications

General IconGeneral
Programming LanguageSTEP 7 (LAD, FBD, STL, SCL, GRAPH)
Communication InterfacesMPI, PROFIBUS
Power Supply24 V DC, 120/230 V AC (Power supply modules are separate and chosen based on system requirements)
Operating Temperature0°C to 60°C
MountingRack mounting
ProcessorCPU 412-1, CPU 414-2, CPU 416-2, CPU 417-4 (Different CPUs offer varying performance and features)
Relative Humidity5 to 95% (non-condensing)