Application and functions
1.6 Performance data
CP 443-1 OPC UA
16 Operating Instructions, 01/2017, C79000-G8976-C427-02
1.6.2
Configuration limits - communication
OPC functions - OPC UA server
In server mode the CP supports the following configuration limits:
Number of connections to OPC UA clients
Maximum of 10 connections to OPC UA clients
Number of items in the CPU data area
For the variables in the data area of the CPU to be written or read as items, the following
maximum values apply:
Maximum number: 64000 Items (symbols / variables)
Maximum memory requirements 64000 bytes
The maximum memory area is divided among the variables used for OPC UA. As a
consequence the following maximum configuration limits apply to the different data types
of the variables:
64000 variables of the data type BOOL
or
64000 variables of the data type BYTE
or
32000 variables of the data type WORD
or
16000 variables of the data type DWORD
or a combination of the maximum values listed, for example:
32000 variables of the data type BYTE
+ 8000 variables of the data type WORD
+ 4000 variables of the data type DWORD
Number of supported subscriptions
Maximum of 5 subscriptions per session
In total maximum of 50 subscriptions at the same time
Number of items per subscription
Maximum of 900 items per subscription
Maximum of 45000 items over all subscriptions
Memory depth for MonitoredItems
Queue size 2