Operating Instructions, 01/2017, C79000-G8976-C427-02
35
Configuration and operation
4
4.1
Controlling the mode
Changing the mode
You can change the mode of the CP between RUN and STOP using STEP 7 or using
STEP 7 special diagnostics.
STOP → RUN
During startup, the CP adopts configured and/or downloaded data in the work memory and
then changes to RUN mode.
RUN → STOP
The CP changes to STOP (transitional phase with LED display "Stopping").
The reaction is as follows in STOP:
Established connections (OPC UA) are terminated
The following the functions are disabled:
Time-of-day synchronization
The following functions remain enabled:
The configuration and diagnostics of the CP (system connections for configuration,
diagnostics, and PG channel routing are retained);
Web diagnostics
4.2
Security recommendations
Keep to the following security recommendations to prevent unauthorized access to the
system.
General
You should make regular checks to make sure that the device meets these
recommendations and other internal security guidelines if applicable.
Evaluate your plant as a whole in terms of security. Use a cell protection concept with
suitable products.
Do not connect the device directly to the Internet. Operate the device within a protected
network area.