Technical data
20.2 Technical specifications of the CPU 414–5H PN/DP; (6ES7 414-5HM06–0AB0)
S7-400H
System Manual, 03/2012, A5E00267695-11
403
3rd interface
Interface designation X5
Type of interface PROFINET
Physics Ethernet RJ45
2 ports (switch)
Electrically isolated Yes
Autosensing (10/100 Mbps) Yes
Autonegotiation Yes
Auto-crossover Yes
Media redundancy Yes
System redundancy Yes
Changeover time on line interruption, typical
200 ms (PROFINET MRP)
Number of nodes on the ring, max.
50
Change of the IP address at runtime, supported No
Keep Alive function supported Yes
Functionality
PROFINET
Yes
Utilities
PG communication
Yes
OP communication
Yes
S7 communication
Maximum number of configurable connections
Maximum number of instances
Yes
64, one of each reserved for programming device
and OP
2500
S7 routing
Yes
PROFINET IO controller
Yes
PROFINET I-Device
No
PROFINET CBA
No
Open IE communication
over TCP/IP
Yes
ISO-on-TCP
Yes
UDP
Yes
Time synchronization
Yes