Addressing
6.1 Slot-oriented address allocation for modules (default addresses for centralized I/O)
SIMOTION C
134 Operating Instructions, 02/2012
Module start addresses
The following table shows the assignment of module start addresses to slot numbers and
racks.
In the case of input/output modules, the input addresses and output addresses start from the
same module start address.
Table 6- 1 Module start addresses of signal modules
Module
carrier
Module start
addresses
Slot number
1 2 3 4 5 6 7 8 9 10 11
0 Digital
Analog
1)
PS SIMOTION C IM 365 S 0
256
4
272
8
288
12
304
16
320
20
336
24
352
28
368
1 Digital
Analog
1)
- - IM 365 R 32
384
36
400
40
416
44
432
48
448
52
464
56
480
60
496
1)
The FM and CP modules are assigned to the analog address range.
Note
Do not insert any non-configured modules centrally. Modules that are installed but not
configured are repeatedly addressed via the I/O bus. This requires additional computing
time.