Getting Started, 04/2018, FW V4.7 SP10, A5E36100338B AG
27
Installation
3
DANGER
Operation with ungrounded (IT) mains supplies can produce extremely dangerous
conditions
The converter must always be grounded. If the converter is not grounded correctly,
extremely dangerous conditions may arise within the inverter which could prove potentially
fatal.
The converter can only be used on TT and TN mains supplies.
DANGER
Risk of burns and fire due to high temperatures
During operation and for a short time after switching the converter off, the surfaces reach
temperatures that can inflict burns or start fires!
Before attempting to touch the surfaces of the converter, ensure that enough time is given
to allow the converter to cool down to a safe temperature to avoid personal injury.
Remove any flammable materials from around the converter to reduce the risk of fire.
WARNING
Direct current on the PE conductor
This product can cause a direct current on the PE conductor.
If the wrong type of protection device is used, then the expected protection by such a
device could fail to provide the expected protection.
If a residual current device (RCD) is used to provide protection in case of direct or indirect
contact,
only a type B RCD
may be used on the power supply side of this product.
WARNING
Use Only 75°C copper cable for all mains cables
Due to the high internal temperatures, that may exist within the converter housing of the
SINAMICS G110M converter, it is possible that any mains cables that are rated below 75°C
could suffer the loss of their insulating properties.
Therefore, all mains cables used with the SINAMICS G110M converter MUST be at least
75°C copper cables.
In addition, to comply with the UL requirements, all mains cables MUST be only 75°C
copper cables.

Other manuals for Siemens SINAMICS G110M