Installation
3.3 Electrical Installation
Distributed converter for SIMOGEAR geared motors
62 Getting Started, 04/2018, FW V4.7 SP10, A5E36100338B AG
Cable protection
Cable protection for individual converters
If you individually protect an Inverter, then you must protect the Inverter feeder cable using a
fuse.
Table 3- 6 Individual fuse protection
0.75 kW 6SL3517-1BE12-3AM0 FSA 10 A 3NA3803
1.5 kW 6SL3517-1BE14-3AM0 FSA 10 A 3NA3803
For additional information, please refer to Catalog D31at the following link:
SINAMICS and motors for Single-Axis Drives D31 catalog
(
https://intranet.automation.siemens.com/mcms/infocenter/content/en/Pages/order_form.asp
x?nodeKey=key_566000&infotype=catalogs&linkit=null)
Installation using power-through daisy chain
The SINAMICS G110M system has been designed to allow a converter to utilize power-
through to provide the mains power for a number of converters in a daisy chain.
The maximum current limits for the daisy chain are given below:
● For the HanQ variants the maximum current of the daisy chained converters must not
exceed 16 A.
● For the Glanded variants the maximum current on the daisy chained converters must not
exceed 12 A.
● For both HanQ and Glanded variants the input for the daisy chained converters can be
protected by a 20 A fuse.
It is the users responsibility to ensure that the current limits are not exceeded.
The methodology for daisy chaining a number of Inverter is shown in the following diagram.