Installation
3.1 Mechanical Installation
Distributed converter for SIMOGEAR geared motors
Getting Started, 04/2018, FW V4.7 SP10, A5E36100338B AG
29
Clearance distance
The G110M system requires a minimum clearance distance around and above the converter
of 150 mm.
Figure 3-2 G110M Clearance distances
Terminal Housing dimensions and fixing points
The Terminal Housing of the G110M system replaces the existing terminal box on the
connected motor. There are three different types of the Terminal Housings and they are
shown in the following figure. All three Terminal Housings have the same external
dimensions:
Height: 92 mm.
Width: 161 mm
Depth: 171 mm
Please note that the fixing points (for securing the Terminal Housing to the motor) are
indicated in RED. The FS 80/90 Terminal Housing has six fixing points, two of which are
marked in GREEN and indicated by the ground symbol. These fixing points provide the
correct earthing between the Terminal Housing and the motor and MUST be used.
All fixing bolts for the Terminal Housing are supplied with each Terminal Housing.
Note
FS 80/90 Terminal Housing 21 mm fixing screws
The 21 mm fixing screws for the FS 8
0/90 Terminal Housing are not supplied with the
product.