Installation
3.2 System Installation
Distributed converter for SIMOGEAR geared motors
Getting Started, 04/2018, FW V4.7 SP10, A5E36100338B AG
47
● When using the 24 V PSU there is no longer any isolation between the 24 V PSU and the
digital outputs of the system.
● Since the 24 V PSU utilizes the DC link voltage to provide the 24 V supply to the Control
Module, when the mains supply is disconnected, all power will be lost to the Control
Module.
1. Disconnected all power supplies to the system and wait 5 minutes.
2. Remove the Power Module (PM).
3. Remove the blank plate from the side of the terminal housing.
4. Remove the Control Module (CM).
5. Fit the 24 V PSU to the side of the terminal housing, ensuring that no cables or wiring are
trapped between the 24 V PSU and the terminal housing. Tightening torque: 1.5 Nm.
6. Connect the input cable to the DC link terminals in the terminal housing (black to DC- and
red to DC+).
7. The 4-way 24 V cable is routed underneath and then over the top of the CM.
8. Fit the 4-way connector as shown in the illustration below.
9. Fit the CM back into place - ensuring that it securely fastened into place.
10.Replace the PM.
11.Fit blanking cap to the 7/8th connector (note: there is no 7/8th connector on the USS
variant and the AS-i variant has no 7/8th connector or terminals).
12.Power can now be restored to the system.
Figure 3-7 Fitting the input and output connections