Commissioning
4.2 Wiring example for the factory settings
Distributed converter for SIMOGEAR geared motors
Getting Started, 04/2018, FW V4.7 SP10, A5E36100338B AG
67
Figure 4-3 Macro 7 - Switch over between fieldbus and jogging using DI 3 (default DP/PN)
Figure 4-4 Macro 30 - ASi Single slave with fixed setpoints (default ASi)
Note
Unswitched and switched power supply
The unswitched 24
V power supply (also known as non-
switched) on X1.2 and X1.4 provides
power to the general electronics of the Control Unit. The switched 24
V power supply on
X1.1 and X1.5 supplies power for the two digital outpu
ts (DI0 and DI1).
For a complete explanation of the unswitched and switched 24 V supplies and their
limitations, please read the FAQ at the following link:
Unswitched and switched 24 V supply
(http://support.automation.siemens.com/WW/view/en/26986267
)