Commissioning
4.7 Quick commissioning with a PC
Distributed converter for SIMOGEAR geared motors
88 Getting Started, 04/2018, FW V4.7 SP10, A5E36100338B AG
Set the most important parameters to suit your application.
Application:
● [0]: In all applications that do not fall under [3]
● [3]: Applications involving pumps and fans with optimized efficiency. The setting only
makes sense for steady-state operation with slow speed changes.
Motor identification:
● [1]: Recommended setting for "speed control" control type. Measure the motor data at
standstill and with the motor rotating. The inverter switches off the motor after the motor
data identification has been completed.
● [2]: Measure the motor data at standstill. The inverter switches off the motor after the
motor data identification has been completed.
Recommended setting for the following cases:
– You have selected "Speed control" as control mode, however the motor cannot freely
rotate, e.g. for mechanically limited traversing sections.
– You have set "V/f control" as control mode.
● [3]: Measure the motor data while the motor is rotating. The inverter switches off the
motor after the motor data identification has been completed.
Calculating the motor parameters: Select "Complete calculation".
Set the check mark for "RAM data to EEPROM (save data in the drive)" to save your data in
the inverter so that it is not lost if the power fails.
Press the "Finish" button.
You have entered all of the data that is necessary for the quick commissioning of the
inverter.
❒