9.1 Grounding the system
WARNING
High voltage after shutdown
High voltages are still present in the drive even after it has been shut down. Touching the
drive can result in death or serious injury.
Only work on the power unit if it has been sufficiently grounded. Before touching the drive,
ensure that the following parts of the power unit are de-energized:
Internal busbars
Input and output terminals
Auxiliary power supply
Always observe the five safety rules (Page 15)when carrying out any work on the device.
Use a three-pole grounding harness for fixed ball points to ground the system.
Note
Ordering a grounding harness
You can order the grounding harness. Contact the Service Center.
Note
Number of grounding harnesses
Depending on the configuration of the drive, use a sufficient number of grounding harnasses.
A grounding harness is required for each three-phase system.
Secure the clamps for the grounding spider to the ball heads and .
Figure 9-1 Example: Grounding points
Maintenance
9.1 Grounding the system
SINAMICS GL150 6SL38503UM114PA0Z
104 Operating Instructions 04/2017