Other ambient conditions
Table B-9 Other ambient conditions
Storage with suitable packag‐
ing
Transport with suitable pack‐
aging
Operation
Biological ambient conditions
according to class
1B1 according to DIN EN
60721‑3‑1 (IEC 60721‑3‑1)
2B1 according to DIN EN
60721‑3‑2 (IEC 60721‑3‑2)
3B1 according to DIN EN
60721‑3‑3 (IEC 60721‑3‑3)
(without harmful flora)
Chemically active substan‐
ces according to class
1C1 according to DIN EN
60721‑3‑1 (IEC 60721‑3‑1)
2C1 according to DIN EN
60721‑3‑2 (IEC 60721‑3‑2)
3C1 according to DIN EN
60721‑3‑3 (IEC 60721‑3‑3)
Mechanically active substan‐
ces according to class
1S1 according to DIN EN
60721‑3‑1 (IEC 60721‑3‑1)
2S1 according to DIN EN
60721‑3‑2 (IEC 60721‑3‑2)
3S1 according to DIN EN
60721‑3‑3 (IEC 60721‑3‑3)
B.7 Power unit
B.7.1 Connection version, 6/6-pulse
&8
36$
165
065
'5,9(&/L4
=
=
3 ~
M
3 ~
Figure B-1 6-pulse circuit on the line and motor sides.Number of thyristors connected in series 1 or
2).
B.7.2 Terminal blocks
B.7.2.1 Auxiliary voltage supply
Table B-10 Terminal assignment for the auxiliary voltage supply
Converter type Terminal
block
KL for Voltage/current (50 Hz
devices)
Recommended line-
side
fuse
Starting converter:
12-pulse system
‑X9 1
3
5
Cabinet fan 3 ~ 50 Hz 400 V
approx. 16.5 A
25 A
3 ~ 60 Hz 460 V
approx. 23.5 A
35 A
Technical specifications and drawings
B.7 Power unit
SINAMICS GL150 6SL38503UM114PA0Z
Operating Instructions 04/2017 143