3.5.6 Plug connection between the starting converter and excitation equipment (option
G57)
Three plug connections are provided in the cutout in the side panel. This is used to connect
the power unit of the starting converter with the open-loop control cabinet of the excitation
equipment. The sockets are permanently installed in the open-loop control cabinet side panel.
The corresponding connectors in the converter can be freely connected to the terminals with
the adequate lengths provided.
The connectors are defined for the following signal and supply voltages:
Table 3-2 Connector assignment for voltages less than 60 V
Signal name Pin assignment = MBJ01DE001.CX-X24
24 V DC supply voltage P24V 1
2
3
4
M24V
Enable signal from the starting converter power
unit
P24V 5
Signal 6
Protective trip from the starting converter power
unit
P24V 7
Signal 8
Protection of the damping element OK (optional) P24V 9
Signal 10
Reserve Reserve
11
12
Reserve 13
14
Reserve 15
Table 3-3 Connector assignment for battery and voltages greater than 60 V (1AC)
Signal name Pin assignment = MBJ01DE001.CX-X22
230 V AC 50 Hz supply voltage (this voltage can
differ depending on the particular country)
L 1
N 2
Reserve Reserve 3
Reserve 4
220 V DC battery voltage (this voltage can differ
depending on the particular country)
L+ 5
L- 6
Table 3-4 Connector assignment for voltages greater than 60 V (3 AC)
Signal name Pin assignment = MBJ01DE001.CX-X40
400 V AC 50 Hz supply voltage (this voltage can
differ depending on the particular country)
L1 1
L2 2
L3 3
Description
3.5 Options
SINAMICS GL150 6SL38503UM114PA0Z
44 Operating Instructions 04/2017