8.4.3 Uncontrolled stop, EMERGENCY STOP category 0
Function
This function concerns the stop category 0 EMERGENCY STOP for an uncontrolled stop in
accordance with EN 60 204-1. The function enables the voltage to be isolated via the circuit
breaker. The motor coasts down.
The safety shutdown is based on a single circuit. Protection against wire breakage is assured
due to the use of circuit breakers with undervoltage release. The emergency stop button used
is forced.
The following markings have the function:
Use of proven components
Suitable for the intended use
The occurrence of a fault can result in the loss of the safety function.
The probability of a fault occurring is reduced as far as possible by the use of forced contacts.
The use of a single circuit in conjunction with undervoltage release achieves compliance with
safety category 1 to EN 954-1.
Note
This has not been officially certified in Germany.
Connecting
Firstly, the contacts of the EMERGENCY STOP button are integrated into the circuit breaker
control circuit. Secondly, the remaining NC contact is connected to the terminal block.
EMERGENCY STOP button Where connected
=.DB-S1001:31-32 EMERGENCY STOP customer =.DB-X05:9, 10
Max. connectable cross-section: 4 mm² (AWG 10)
Activation of the circuit breakers is described in the section entitled "Connecting the circuit
breakers".
Operation
8.4 Monitoring and protection functions
SINAMICS GL150 6SL38555UN113KA0Z
Operating Instructions Rev.201910281450 EXAMPLE 113