3.2.3 External safety components
The safety concept of the converter is supplemented by the following external components:
Circuit breaker
You can find more detailed information in the section "Circuit breaker (provided by the
customer)".
Input-side transformer
When an error is detected, the medium-voltage transformer limits the short-circuit current
and is configured in such a way that the maximum permissible short-circuit current (see the
technical data) is not exceeded.
3.2.4 Protection and monitoring functions of internal components
The internal components of the converter have the following protection and monitoring
functions:
Converter protection based on monitoring systems:
Current monitoring
Output voltage monitoring
Thermal monitoring of the DC link reactor
Insulation monitoring
Supply voltage monitoring
Circuit breaker monitoring
Heat exchanger unit monitoring
Shutdown in the event of semiconductor failure
Shutdown in the event of control component failure
Internal protection functions for the control hardware
Protection against communication failure between the closed-loop control and the power
unit
Anti-condensation heating
3.2.5 Protection and monitoring functions for external components
Transformer and motor can be monitored in the device. A fast protective shutdown that you can
activate for external problems, e.g. short-circuits, is present.
Description
3.2 Safety concept
SINAMICS GL150 6SL38555UN113KA0Z