Menu
6.9 Know-how Protection
Intelligent Operator Panel (IOP)
Operating Instructions, 08/2015, FW V1.6.1, A5E00110011B AF
93
As previously stated, after commissioning the Inverter and checking that parameters have
been set correctly, the number of parameters to included in the exception list must be
determined and set in parameter p7763. To set the number of parameters to be included in
the exception list the following procedure must be performed. When establishing the first
exception list, some parameters may already be entered into the exception list; under no
circumstances should you remove these parameters from the exception list as these are
essential parameters that must remain in the exception list.
1.
Select "Menu" from the main screen.
2.
Select "Parameters" from the menu.
3.
Select "Search by number" from the Parameters menu.
4.
Input "07763" then press "OK"