Controlling the safety functions 
  5.2 Control of "STO" and "SS1" via terminal module for option K82 
Safety Integrated 
Function Manual, 08/2023, A5E03264275A 
43 
Recommended application 
This option is used when the following requirements apply: 
•  Control is realized with electrical isolation in a voltage range 24 V DC/AC. 
•  Using non-shielded control lines which are longer than 30 m. 
•  The devices are deployed in plants dispersed over a wide area (no ideal equipotential 
bonding). 
Principle of operation 
Two independent channels of the integrated safety function are controlled via relays (-K41, 
-K42). 
Relay -K41 controls the signal at the Control Unit that is necessary for the safety function and 
relay -K42, the corresponding signal at the Motor Module. 
The selection and deselection must be simultaneous. The time delay that is unavoidable due 
to mechanical switching operations, for example, can be adapted via parameters. p9650 
specifies the tolerance time within which selection/deselection of the two monitoring 
channels must take place to be considered as "simultaneous". 
The circuit is structured so that it is protected against wire break, i.e. if the relay's control 
voltage fails then the safety function is active. 
A feedback signal is not part of the safety concept. 
Note 
The feedback signal is not necessary to comply with standard ISO
 13849-1 Cat. 3 PL d and 
The selection of the safety function must be performed in two channels. A switch according 
to ISO 13850, positive opening according to IEC 60947-5-1 or a certified safety control must 
be used as actuating element. 
 
Failure of the safety functions as a result of an unsuitable actuating element 
An unsuitable actuating element may cause the safety function to fail which can result in 
death or serious injury. 
•  Select the correct actuating element to comply with the standard to be complied with 
(ISO 13849-1 Cat. 3 PL d or IEC 61508 SIL 2) for the complete system. 
Forced checking procedure 
The maximum value for the forced checking procedure interval when using option K82 is 
12 months (8760 h).