Controlling the safety functions
5.7 Motion monitoring without selection
Safety Integrated
Function Manual, 08/2023, A5E03264275A
99
5.7 Motion monitoring without selection
As an alternative to controlling via terminals and/or PROFIsafe, there is also the option to
parameterize several safety functions without selection. For this mode, after
parameterization and a POWER ON, these functions are permanently selected.
Example
"SLS without selection" can be used, for example, to monitor the maximum velocity to
prevent that the drive exceeds a mechanical speed limit. For this purpose, using the "without
selection" function, an F-DI does not have to be used; an F-CPU is also not required.
Features
The function "Motion monitoring without selection" is available in the following versions:
p9601
Meaning
Functionality
Comment
0024 hex
Drive-integrated motion monitoring
functions without selection are ena-
bled
SLS
SDI
p9501.0 = 1
p9501.17 = 1
0025 hex
Drive-integrated motion monitoring
functions without selection with STO
via terminals are enabled
SLS
SDI
STO
SS1
SBC
p9501.0 = 1
p9501.17 = 1
Basic Functions
Basic Functions
Basic Functions
The functions "SLS without selection" and "SDI without selection positive/negative" are
selected with p9512.
The functions without selection are available in the versions "with encoder" and "without
encoder" (selection via p9506).
The functions without selection are parameterized and enabled in the same way as the
versions with control via PROFIsafe/terminals.
Acknowledging safety faults
For acknowledging safety faults, a distinction should be made between the following cases:
Drive-integrated motion monitoring functions without selection
Acknowledging safety faults is only possible with POWER ON.
Drive-integrated motion monitoring functions without selection and Basic Functions via
onboard terminals
Acknowledging Safety faults is possible with POWER ON or selecting/deselecting STO or
SS1.