Controlling the safety functions   
5.3 Control of "STO" and "SS1" via terminals on the Control Unit and the Motor/Power Module 
  Safety Integrated 
56  Function Manual, 08/2023, A5E03264275A 
•  If the "Safe Stop 1" of the Basic Functions is not selected within the tolerance time in two 
channels, this is detected by the cross-check, and fault F01611 (STOP F) is output. After 
the set "SI Safe Stop 1 delay time" (p9652), the pulses are suppressed. 
Note 
To enable the drive to brake to standstill even when selected through one channel, the 
time in p9652 must be shorter than the sum of the parameters for the data cross
-check 
(p9650 and p9658). Otherwise, the drive will coast down after the time p965
0 + p9658 
Further notes for setting the discrepancy time are contained in the List Manual for the 
following messages 
•  F01611 (Basic Functions) 
•  C01770 (Extended/Advanced Functions) 
Overview of important parameters 
 
 
SI SGE switchover discrepancy time (Control Unit) 
 
SI Safe Stop 1 delay time (Control Unit) 
 
SI transition time STOP F to STOP A (Control Unit) 
 
SI Motion F-DI switchover discrepancy time (processor 1)