Closed-loop operation above approx. 1 Hz (p1755) and the ability to start or reverse at 0 Hz
directly in closed-loop operation (p1750) produce the following benefits:
No switching action within the closed-loop control necessary. This means smooth behavior,
no frequency drops.
Stationary speed–torque control up to approx. 1 Hz.
Note
For controlled reversing or controlled starting for 0 Hz, under the following condition the
closed-loop control is switched automatically from closed-loop controlled operation to open-
loop controlled operation:
Dwell-time > 2 seconds or > p1758 in the range of 0 Hz
8.5.1.3 U/f control
As an alternative to vector control, a U/f control is available for induction motors. This technique
is only appropriate when there are no highly dynamic requirements, e.g. pumps and fan drives.
V/f control aims to maintain a constant flux Φ in the motor whereby the flux (Φ) is proportional
to the magnetization current (Iµ) and the ratio of voltage (V) to frequency (f).
Φ ~ Iµ ~ V/f
The torque (M) generated by the induction motors is, in turn, proportional to the vector product
(Φ x I) of the flux and current. The V/f characteristic is derived from these basic premises:
To generate as much torque as possible with a given current, the motor must function using the
greatest possible constant flux. To maintain a constant flux (Φ), therefore, the voltage must be
changed in proportion to the frequency f. The voltage change ensures that a constant
magnetization current Iµ flows.
I
803˓
0
Q
˓
Q
I
Q
I
PD[
0˓
83
83
3RLQWRIPRWRU
)LHOGUDQJH
9ROWDJHUDQJH
Figure 8-4 Operating areas and characteristic curves for the induction motor with drive supply
Adjustable parameters
Parameter Setting
p1300 Open-loop/closed-loop operating mode / control type
Operation
8.5 Functions
SINAMICS SM150 6SL3845-7NN46-7AA2
Operating Instructions Rev.201910281345 EXAMPLE 113