Example: Changing analog output 0 from current to voltage output –/+ 10 V
9ROWDJHRXWSXWSUHVHQWDWWHUPLQDOJURXQGLVDWWHUPLQDO
6HWDQDORJRXWSXWW\SHWR99
;
S 
Figure 8-5 Example: Setting analog output 0
Example: Changing analog output 0 from current to voltage output / +10 V and setting the characteristic
;
Voltage output present at terminal 1, ground is at terminal 2
S>@ 
Set TM31.AO_type [analog output 0] to between -10 and +10 V.
S>@ 
Set TM31.AO_char. x1 to 0.00%.
S>@ 
Set TM31.AO_char.
1 to 0.000 V.
S>@ 
Set TM31.AO_char. x2 to 100%.
S>@ 
Set TM31.AO_char. y2 to 10.000 V.
Factory setting
Digital output Terminal Factory setting
DO0 X542: 2,3 "Pulses enabled"
DO1 X542: 5,6 "No fault"
DI/DO8 X541: 2 "Ready for switching on"
DI/DO9 X541: 3
DI/DO10 X541: 4
DI/DO11 X541: 5
8.5.2.2 Additional settings for analog outputs
Two signals are freely available for each TM31, which can be used to output the analog signals.
Operation
8.5 Functions
SINAMICS SM150 6SL3845-7NN46-7AA2
116 Operating Instructions Rev.201910281345 EXAMPLE