Attaching the grounding spider
Secure the clamps for the grounding spider to the ball heads and .
;
Ball heads
Figure 9-3 Attaching the grounding spider
9.2.2 Grounding using a make-proof grounding switch
The drive is equipped with a make-proof grounding switch (in compliance with the requirements
of IEC61800-5-1, Section 4.2.13).
You can close the make-proof grounding switch when the doors are closed and only at a
voltage below 60 V. If the auxiliary voltage fails completely, the make-proof grounding switch
cannot be closed. It is not permissible that you open the doors before the make-proof grounding
switch is closed.
WARNING
Danger to life as a result of a DC link short-circuit
A DC link short-circuit can occur if you ground the drive under voltage. This can result in death,
serious injury or material damage.
Remove the socket wrench before switching on the power. This activates the interlocking.
Maintenance
9.2 Grounding the system
SINAMICS SM150 6SL3845-7NN46-7AA2