9.5.11 Replacing the precharging transformer
WARNING
Danger to life as a result of incorrect replacing the precharging transformer
Replacing the precharging transformer incorrectly can result in death, serious injury, or
material damage.
Follow "the five safety rules (Page 15)".
Before replacing the precharging transformer, open the safety disconnector for the 400 V
supply.
Lift the transformer carefully because it is heavy (> 45 kg).
Removing the precharging transformer
1. Detach the 400 V connecting cables .
2. Remove the high-voltage cables .
3. Release the PE conductor.
4. Remove the fixing screws on the base brackets .
5. Remove the transformer.
Figure 9-26 Example: Replacing the precharging transformer
Maintenance
9.5 Repair
SINAMICS SM150 6SL3845-7NN46-7AA2
Operating Instructions Rev.201910281345 EXAMPLE 167