The circuit breaker is controlled and enabled from the closed-loop control. If this has not
been enabled, under no circumstances should you close the circuit breaker using external
mechanical or electrical means.
To protect the converter transformer, ensure that overcurrent protection is in place.
3.5.10 Converter transformer
A two-winding transformer is required for each Active Line Module. When two complete drive
units are connected in parallel, a three-winding transformer with shifted windings can be used
for suppressing line harmonics.
Consider the following properties during the configuration:
Transformer secondary voltage: 3.3 kV
Minimum leakage inductance: 1 mH
(short-circuit voltage
u
k
=15% to 28% depending on transformer output)
This value includes all the inductance between the line and the converter: Line short-circuit
inductance, transformer inductance, reactor inductance.
Transformer taps for voltage adjustments: 2 x ± 2.5
The winding taps are usually located on the high voltage side of the transformer.
Design the transformer for the following loads:
Max. dU/dt stress at the inverter input terminals: 6 kV/µS
Peak voltage load phase-phase and phase-ground: 8.4 kV
Current load with DC component: approx. 4 A to 5 A
3.5.11 Actual value acquisition
Actual current and voltage values are recorded by the AVT combination module . The AVT
combination module converts analog signals into digital signals and forwards them to the PSA.
The signals are transferred to the PSA via fiber-optic cables.