3. Mount the flexible link rail "V2" . Tighten all screws with a torque of 50 Nm.
Busbar mounting points, bolt length 45 mm
Spacer, bolt length 70 mm
Spacer mounting points, bolt length 70 mm
Flexible busbar "V2"
First screw the three spacers onto the link rail.
Screw the link rail left and right onto the two fastening points of the busbars "A2".
Screw the link rail onto the spacers.
4. Mount the flexible link rail "V3" . Tighten all screws with a torque of 50 Nm.
Busbar mounting points, bolt length 45 mm
Spacer mounting points, bolt length 70 mm
Flexible busbar "V3"
Screw the link rail left and right onto the two fastening points of the busbars "A3".
Screw the link rail onto the spacers.
Installation
5.8 Connecting the DC bus
SINAMICS SM150 6SL3845-7NN46-7AA2
Operating Instructions Rev.201910281345 EXAMPLE 85