SINAMICS V20 Inverter 
12  A5E37281078-003, 05/2016 
User terminals for FSAA/FSAB: 
User terminals for FSA to FSE: 
To disconnect the integrated EMC filter on FSE from the ground, you can use a Pozidriv or flat-bit screwdriver to remove the 
EMC screw. 
Damage to the mains terminals 
During electrical installation of the inverter frame sizes A and B, use stranded cables or cables with UL/cUL-certified, 
suitable fork crimps rather than solid cables or cables with pin crimps for mains terminal connection; for frame size E, use 
cables with UL/cUL-certified ring crimps for the mains terminal connections. 
Recommended cable cross-sections and screw tightening torques 
Motor / DC / braking resistor / output earth 
terminals 
Screw tightening torque 
(tolerance: ± 10%) 
Screw tightening torque 
(tolerance: ± 10%) 
B  3.0 kW to 4.0 kW  6 mm
2
 (10)  6 mm
2
 (10) 
1.5 Nm