Parameter
Description
Range
Factory default
Acc.
level
P0003
User access level
0 - 4
1
1
0 Use-defined parameter list (defines a limited set of parameters to which the end user has access. See
P0013 for details on use.)
1
Standard (allows access into most frequently used parameters)
2
Extended (allows extended access to more parameters
3
Expert (for expert use only)
4
Service (only for use by authorized service personnel, password protected)
P0004
Parameter filter
0 - 24
0
1
0
All parameters
12
Inverter features
2
Inverter
13
Motor control
3
Motor
19
Motor identification
5
Technology application / units
20
Communication
7
Commands, binary I/O
21
Warnings / faults / monitoring
8
Analog input and analog output
22
Technology controller
10
Setpoint channel / RFG
24
List of modified parameters
P0005
Parameter display selection
0 - 9580
0
2
Selects default display parameter (inverter display).
Example:
The inverter displays the value of the parameter selected here by default.
P0010
Commissioning parameter
0 - 30
0
1
0
Ready
29
Download
1
Quick commissioning
30
Factory setting
2
Inverter
r0018
Firmware version
-
-
1
r0021
CO: Actual filtered frequency [Hz]
-
-
2
r0025
CO: Actual output voltage [V]
-
-
2
r0026[0]
CO: Actual filtered DC-link voltage [V]
-
-
2
r0027
CO: Actual output current [A]
-
-
2
r0031
CO: Actual filtered torque [Nm]
-
-
2
r0032
CO: Actual filtered power
-
-
2
r0035[0...2]
CO: Actual motor temperature [°C]
-
-
2
r0039
CO: Energy consumpt. meter [kWh]
-
-
2
P0040 Reset energy consumpt. and energy
saved meter
0 - 1 0 2
0
No reset
1
Reset r0039 to 0
P0042[0...1]
Energy saving scaling
0.000 - 100.00
0.000
2
Index:
[0]
Factor for kWh to currency conversion
[1]
Factor for kWh to CO2 conversion
r0043[0...2]
Energy saved [kWh]
-
-
2
r0050
CO / BO: Active command data set
-
-
2
r0051[0...1]
CO: Active inverter data set (DDS)
-
-
2
r0052.0...15
CO / BO: Active status word 1
-
-