SINAMICS V20 Inverter
22 A5E37281078-003, 05/2016
3.2.5
Setting common parameters
Parameter
Description
Parameter
Description
P1080[0] Minimum motor frequency P1001[0] Fixed frequency setpoint 1
P1082[0] Maximum motor frequency P1002[0] Fixed frequency setpoint 2
P1120[0] Ramp-up time P1003[0] Fixed frequency setpoint 3
P1121[0] Ramp-down time P2201[0] Fixed PID frequency setpoint 1
P1058[0] JOG frequency P2202[0] Fixed PID frequency setpoint 2
P1060[0] JOG ramp-up time P2203[0] Fixed PID frequency setpoint 3
P1061[0] JOG ramp-down time
3.3
Restoring to defaults
Parameter
Function
Setting
P0003 User access level = 1 (standard user access level)
P0010 Commissioning parameter = 30 (factory setting)
P0970 Factory reset = 1: parameter reset to user defaults if stored, else factory de-
faults (restoring to user defaults)
= 21: parameter reset to factory defaults deleting user defaults if
stored (restoring to factory defaults)
After the setting for P0970, the inverter displays "8 8 8 8 8" and then the screen shows "P0970". P0970 and P0010 are
automatically reset to their original value 0.
4
Technical support information
Country
Hotline
China +86 400 810 4288
France +33 0821 801 122
Germany +49 (0) 911 895 7222
Italy +39 (02) 24362000
Brazil +55 11 3833 4040
India +91 22 2760 0150
Korea +82 2 3450 7114
Turkey +90 (216) 4440747
USA +1 423 262 5710