SINAMICS V20 Inverter
14 A5E37281078-003, 05/2016
Three phase AC 400 V inverters
Single phase AC 230 V inverters
Line supply characteristics
1)
Voltage range 380 V to 480 V AC (tolerance: -15 % to +10 %)
2)
47 Hz to 63 Hz
Current derating exists at the input voltages /
switching frequencies higher than 400 V / 4kHz.
200 V to 240 V AC (tolerance: -15 % to +10 %)
2)
47 Hz to 63 Hz
Current derating exists at the input voltages /
switching frequencies higher than 230 V / 8kHz.
Overvoltage catego-
ry
EN 60664-1 Category III
Permissible supply
configuration
TN, TT, IT: FSA to FSE (unfiltered); FSE (fil-
tered)
3)
TN, TT with grounded neutral: FSA to FSE
TN, TT: FSAA to FSC (unfiltered)
TN, TT with grounded neutral: FSAA to FSC
IT: FSAA/FSAB (unfiltered)
Supply environment Second environment (private power network) First environment (public power network)
Overload current Rated power 0.12 kW to 15 kW 150% rated for 60 seconds
Rated power 18.5 kW (HO)/22 kW (HO)
Rated power 22 kW (LO)/30 kW (LO) 110% rated for 60 seconds
Surrounding air
temperature
- 10 °C to 40 °C: without derating
40 °C to 60 °C: with derating (UL/cUL-compliant: 40 °C to 50 °C, with derating)
Storage temperature - 40 °C to + 70 °C
Protection class IP 20
Maximum humidity
level
95% (non-condensing)
Shock and vibration Long-term storage in the transport packaging according to EN 60721-3-1 Class 1M2
Transport in the transport packaging according to EN 60721-3-2 Class 2M3
Vibration during operation according to EN 60721-3-3 Class 3M2
Operating altitude Up to 4000 m above sea level
1000 m to 4000 m: output current derating
2000 m to 4000 m: input voltage derating
Environmental clas-
ses
Pollution degree: 2
Solid particles: class 3S2
Chemical gases: class 3C2 (SO
2
, H
2
S)
Climate class: 3K3
1)
For more information about current deratings, see the SINAMICS V20 Inverter Operating Instructions.
2)
When the input voltage is below the rated value, current deratings are permissible and therefore the voltage-dependent
speed and/or torque may be reduced.
3)
To operate FSE (filtered) on IT power supply, make sure you remove the screw for the EMC filter.