SINAMICS V20 Inverter
A5E37281078-003, 05/2016
21
Description
Default values for connection macros (Cn...)
001
002
003
004
005
006
007
008
009
010
011
P1047[0] MOP ramp-up time of the RFG - - - - - 10 - - - - -
P1048[0] MOP ramp-down time of the RFG - - - - - 10 - - - - -
P1074[0] BI: Disable additional setpoint - - - - 1025.0 - - - - - -
P2010[0] USS/MODBUS baudrate - - - - - - - - - 8 6
P2011[0] USS address - - - - - - - - - 1 -
P2012[0] USS PZD length - - - - - - - - - 2 -
P2013[0] USS PKW length - - - - - - - - - 127 -
P2014[0] USS/MODBUS telegram off time - - - - - - - - - 500 100
P2021[0] MODBUS address - - - - - - - - - - 1
P2022[0] MODBUS reply timeout - - - - - - - - - - 1000
P2023[0] RS485 protocol selection - - - - - - - - - 1 2
P2034 MODBUS parity on RS485 - - - - - - - - - - 2
P2035 MODBUS stop bits on RS485 - - - - - - - - - - 1
P2200[0] Enable PID controller - - - - - - - 1 1 - -
P2216[0] Fixed PID setpoint mode - - - - - - - - 1 - -
P2220[0] BI: Fixed PID setpoint select bit 0 - - - - - - - - 722.1 - -
P2221[0] BI: Fixed PID setpoint select bit 1 - - - - - - - - 722.2 - -
P2222[0] BI: Fixed PID setpoint select bit 2 - - - - - - - - 722.3 - -
P2253[0] CI: PID setpoint - - - - - - - 755.0 2224 - -
P2264[0] CI: PID feedback - - - - - - - 755.1 755.1 - -
3.2.4
Setting application macros
Functionality
This menu defines certain common applications. Each application macro provides a set of parameter settings for a specific
application. After you select an application macro, the corresponding settings are applied to the inverter to simplify the
commissioning process.
Application macro specific parameters
Parameter
Description
Factory
default
Default for application macro
Remarks
AP010
AP020
AP021
AP030
P1080[0]
Minimum frequency
0
15
20
-
-
Inverter running at a lower speed inhibited
P1300[0] Control mode 0 7 7 0 1 =7: Quadratic V/f
=0: Linear V/f
=1: V/f with FCC
P1110[0] BI: Inhibit negative
frequency setpoint
0 1 - - - Reverse rotation inhibited
P1200[0] Flying start 0 - 2 - - Search for the speed of the running motor
with a heavy inertia load so that the motor
runs up to the setpoint
P1210[0]
Automatic restart
1
2
2
-
-
Restart after mains blackout
P1120[0] Ramp-up time 10 10 10 10 5 Ramp-up time from zero to maximum fre-
quency
P1121[0] Ramp-down time 10 10 20 10 5 Ramp-down time from maximum frequency
to zero
P1312[0] Starting boost 0 - - 30 30 Boost only effective when accelerating for
the first time (standstill)
P1311[0] Acceleration boost 0 - - 0 - Boost only effective when accelerating or
braking
P1310[0] Continuous boost 50 - 50 - Additional boost over the complete fre-
quency range