P1047[0] MOP ramp-up time of the RFG - - - - - 10 - - - - -
P1048[0] MOP ramp-down time of the RFG - - - - - 10 - - - - -
P1074[0] BI: Disable additional setpoint - - - - 1025.0 - - - - - -
P2010[0] USS/MODBUS baudrate - - - - - - - - - 8 6
P2011[0] USS address - - - - - - - - - 1 -
P2012[0] USS PZD length - - - - - - - - - 2 -
P2013[0] USS PKW length - - - - - - - - - 127 -
P2014[0] USS/MODBUS telegram off time - - - - - - - - - 500 100
P2021[0] MODBUS address - - - - - - - - - - 1
P2022[0] MODBUS reply timeout - - - - - - - - - - 1000
P2023[0] RS485 protocol selection - - - - - - - - - 1 2
P2034 MODBUS parity on RS485 - - - - - - - - - - 2
P2035 MODBUS stop bits on RS485 - - - - - - - - - - 1
P2200[0] Enable PID controller - - - - - - - 1 1 - -
P2216[0] Fixed PID setpoint mode - - - - - - - - 1 - -
P2220[0] BI: Fixed PID setpoint select bit 0 - - - - - - - - 722.1 - -
P2221[0] BI: Fixed PID setpoint select bit 1 - - - - - - - - 722.2 - -
P2222[0] BI: Fixed PID setpoint select bit 2 - - - - - - - - 722.3 - -
P2253[0] CI: PID setpoint - - - - - - - 755.0 2224 - -
P2264[0] CI: PID feedback - - - - - - - 755.1 755.1 - -
This menu defines certain common applications. Each application macro provides a set of parameter settings for a specific
application. After you select an application macro, the corresponding settings are applied to the inverter to simplify the
commissioning process.
0 1 - - - Reverse rotation inhibited
P1200[0] Flying start 0 - 2 - - Search for the speed of the running motor
with a heavy inertia load so that the motor