SINAMICS V20 Inverter
4 A5E37281078-003, 05/2016
Outline dimensions
(Unit: mm/inch)
W
H
H1
1)
D
FSAA 68/2.7 142/5.6 - 107.8/4.2 -
FSAB 68/2.7 142/5.6 - 127.8/5 -
FSA 90/3.5 150/5.9 166/6.5 145.5 (114.5
3)
)/5.7(4.5
3)
) -
FSB 140/5.5 160/6.3 - 164.5/6.5 106/4.17
FSC 184/7.24 182/7.17 - 169/6.7 108/4.25
FSD 240/9.4 206.5/8.1 - 172.5/6.8 98/3.9
FSE 245/9.6 216/8.5 264.5/10.4 209/8.2 118.5/4.7
1)
Height of frame sizes with fan(s)
2)
Depth inside the cabinet for push-through mounting
3)
Depth of Flat Plate inverter (400 V 0.75 kW variant only)
Drill patterns
(Unit: mm)
W
H
W1
H1
H2
Ø
Screw
Tightening torque
FSAA/FSAB 58 132 - - - 4.6 2 × M4 1.8 Nm ± 10%
FSA 79 140 - - - 4.6 4 × M4 1.8 Nm ± 10%
FSB 127 135 - - - 4.6 4 × M4 1.8 Nm ± 10%
FSB
2)
125 108 118 172 45.5 4.6 4 × M4 1.8 Nm ± 10%
FSC 170 140 - - - 5.8 4 × M5 2.5 Nm ± 10%
FSC
2)
170 116 161 197 61 5.8 4 × M5 2.5 Nm ± 10%
FSD 223 166 - - - 5.8 4 × M5 2.5 Nm ± 10%
FSD
2)
223 142 214 222 59 5.8 4 × M5 2.5 Nm ± 10%
FSE 228 206 - - - 5.8 4 × M5 2.5 Nm ± 10%
FSE
2)
228 182 219 282 83 5.8 4 × M5 2.5 Nm ± 10%
1)
For FSAA/FSAB, you only need to drill these two holes for cabinet mounting.
2)
For push-through mounting only.
For more information about the push-through mounting and the installation of the Flat Plate inverter, see the SINAMICS V20
Inverter Operating Instructions.