SINAMICS V20 Inverter
A5E37281078-003, 05/2016
9
Inverter power
rating (kW)
Maximum rated
current of circuit
breaker (A)
SCCR of SINAMICS V20
with circuit breaker
Minimum enclo-
sure volume
(m
3
/cu. in.)
2)
230 V AA
to
AB
0.12 to 0.75 15 3RV1742, 3RV2711,
LGG, LGGA, CED6
65 kA, 240 VAC -
A 0.12 to 0.75 15 3RV1742, 3RV2711,
65 kA, 240 VAC 0.47/28681
B 1.1 30 3RV1742, 3RV2711,
LGG, CED6, NCGA,
HCGA
65 kA, 240 VAC 0.80/48819
1.5 30 3RV1742, 3RV2711,
LGG, CED6, NCGA,
HCGA
65 kA, 240 VAC
C 2.2 40 3RV1742, LGG, CED6,
NCGA, HCGA
65 kA, 240 VAC 1.22/74449
3.0 50 3RV1742, LGG, CED6,
NCGA, HCGA, NDGA,
HDGA, LDGA, NDGB,
1)
NCGA and HCGA are UL Listed 3VL11 series (Siemens type VL150x UL) circuit breakers; NDGA, NDGB, HDGA and
HDGB are UL listed 3VL25 series (Siemens type VL150 UL) circuit breakers shown in the European circuit breaker cat-
alog LV 16.
2)
Unventilated enclosure of minimum volume as specified in the table above is required except for 230 V FSAA/FSAB.
There is no minimum enclosure volume requirement for 230 V FSAA/FSAB.
3)
The rated current of Type "3RV1742" circuit breakers with SCCR 65 kA, 480 VAC must be < 35 A.