2.2.4 RS232 mode on FLN 2 and FLN 3
Using FLN 2 or FLN 3 in RS232 mode (for Securitel or Sintony integration) requires
that the EOL jumpers be set to OFF. This entails powering down the ACC-G2,
removing the FLN expansion module and then setting all the jumpers for the
appropriate ports to OFF.
A torx screwdriver bit of size T10 is required to remove the FLN expansion module.
A magnifying glass and a small screwdriver are useful for setting the EOL dip
switches.
See the
AC5102 Technical Manual
in the SiPass integrated software bundle for
more information.
Note: Disregard connections for FLN 2 & 3 shown in Section “Bus Termination of
the FLNs” in
AC5102 Technical Manual
and follow as shown in the table below:
2.2.5 Restoring Default Network and Password Settings
The X992 jumper is near the battery for the Real Time Clock (RTC).
Short the pins of X992 for 3 seconds (using a jumper), until the orange ERROR led
is blinking quickly. Remove the short, and wait about 10 seconds for application to
restart and reset the network settings.
The default network settings are:
IP Address : 192.168.251.1
Subnet Mask : 255.255.255.0
Default Login Credentials: SIEMENS/spirit
All other settings are zeroed, including the SiPass host address and modem
configuration is disabled. The Telnet server is re-enabled.
Use either Telnet, the USB Client Application or the Network Configurator tool to
restore the network settings.