2.4 4101-3 (ACC-Granta)
2.4.1 Configuring using USB Client Application
See section ACC-G2 USB Client Application for details.
2.4.2 Network Discovery
See section ACC and FLN Field Service Network Tool for details.
2.4.3 Restoring Default Network and Password Settings
The X992 jumper is near the battery for the Real Time Clock (RTC)
Short the pins of X992 for 3 seconds (using a jumper), until the orange ERROR led
is blinking quickly. Remove the short, and wait about 10 seconds for application to
restart and reset the network settings.
The default network settings are:
IP Address : 192.168.1.250
Subnet Mask : 255.255.255.0
Default login credentials: SIEMENS/spirit
All other settings are zeroed (including the SiPass host address) and modem
configuration is disabled. The SSH server is re-enabled as well as the Telnet
server.
Use either Telnet, the USB Client Application or the Network Configurator tool to
restore the network settings.