EasyManua.ls Logo

Siemens siprotec 7SD5

Siemens siprotec 7SD5
698 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Functions
138
7SD5 Manual
C53000-G1176-C169-1
Figure 2-41 Polygonal characteristic (setting values are marked by dots)
Determination of
Direction
For each loop an impedance vector is also used to determine the direction of the short-
circuit. Usually similar to the distance calculation, Z
L
is used. However, depending on
the „quality“ of the measured values, different computation techniques are used. Im-
mediately after fault inception, the short-circuit voltage is disturbed by transients. The
voltage memorized prior to fault inception is therefore used in this situation. If the
steady-state short-circuit voltage (during a close-in fault) is even too small for direction
determination, an unfaulted voltage is used. This voltage is in theory quadrilateral to
the actual short-circuit voltage for both phase-earth loops as well as for phase-phase
loops (refer to Figure 2-42). This is taken into account when computing the direction
vector by means of a 90° rotation. In Table 2-11 the allocation of the measured values
to the six fault loops for the determination of the fault direction is shown.
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens siprotec 7SD5

Related product manuals