1.3 Characteristics
29
7SD5 Manual
C53000-G1176-C169-1
Teleprotection
Supplement
(optional)
Different procedures settable
Permissive Underreach Transfer Trip = PUTT (via a separately settable overreach
zone)
Comparison schemes (Permissive Overreach Transfer Trip = POTT or blocking
schemes, with separate overreach zone)
Pilot wire comparison/reverse interlocking (with DC voltage for local connections or
extremely short lines)
Suitable for lines with two or three ends
Phase segregated transmission possible in lines with two ends
Signal exchange between devices via binary outputs and binary inputs, either di-
rectly via device contacts or through the protection data interface(s)
Earth Fault
Protection
(optional)
Time overcurrent protection with maximally three definite time stages (DT) and one
inverse time stage (IDMT) for high resistance earth faults in earthed systems
For inverse-time overcurrent protection a selection from various characteristics
based on several standards is possible
The inverse time stage can also be set as fourth definite time stage
High sensitivity (depending on the version from 3 mA)
Phase current restraint against error currents during current transformer saturation
Second harmonic inrush restraint
Optionally earth fault protection with zero sequence voltage tripping time or inverse
time tripping
Each stage can be set to be non-directional or directional in the forward or reverse
direction
Single-pole tripping enabled by integrated phase selector
Direction determination with zero sequence system quantities (I
0
, U
0
), with zero se-
quence current and transformer star-point current (I
0
, I
Y
), with negative sequence
system quantities (I
2
, U
2
) or with zero sequence power (3I
0
· 3U
0
)
One or more stages may function in conjunction with a teleprotection scheme; also
suited for lines with three ends
Instantaneous tripping by any stage when switching onto a fault
Tripping at Line
Ends with no or
Weak Infeed (op-
tional)
Possible in conjunction with teleprotection schemes
Allows fast tripping at both line ends, even if there is no or only weak infeed avail-
able at one line end
Phase segregated tripping and single-pole automatic reclosure (version with single-
pole tripping)
External Direct and
Remote Tripping
Tripping at the local line end from an external device via a binary input
Tripping of the remote line end by internal protection functions or an external device
via a binary input (with teleprotection)