1 Introduction
30
7SD5 Manual
C53000-G1176-C169-1
Transmission of In-
formation
Transmission of the measured values from all ends of the protected object with the
amount and phase
Transmission of up to 4 fast commands to all remote ends (order option)
Transmission of up to 24 additional binary signals to all remote ends (order option)
Time Overcurrent
Protection
Selectable as emergency function during a failure of the main protection function(s)
due to a failure of the data communication and/or the measuring voltages, or as
backup function;
Maximally two definite time stages (DT) and one inverse time stage (IDMT), each
for phase currents and for earth currents
For inverse-time overcurrent protection a selection from various characteristics
based on several standards is possible
Blocking capability, e.g. for reverse interlocking with any element
Instantaneous tripping by any stage when switching onto a fault
Stub fault protection: fast tripping of faults between the current transformer and line
isolator (when the isolator switching status feed back is available); particularly
suited to substations with 1
1
/
2
circuit breaker arrangements
Instantaneous
High-Current
Switch-onto-Fault
Protection
Fast tripping for all faults on 100 % line length
Selectable for manual closure or following each closure of the circuit breaker
With integrated line energization detection
Automatic Reclo-
sure Function
(optional)
For reclosure after single-pole, three-pole or single-pole and three-pole tripping
Single or multiple reclosure (up to 8 reclosure attempts)
With separate action times for every reclosure attempt, optionally without action
times
With separate dead times after single-pole and three-pole tripping, separate for the
first four reclosure attempts
With the option of an adaptive dead time: in this case only one device controls the
automatic reclosure cycles whilst at the other end(s) the automatic reclosure solely
depends on the one controlling device. The criteria used are voltage measurement
and/or the transmitted CLOSE command (Remote-CLOSE).
Controlled optionally by protection pickup with separate dead times after single,
two-pole and three-pole pickup
Optionally with adaptive dead time, reduced dead time and dead line check
Synchronism and
Voltage Check (op-
tional)
Verification of the synchronous conditions before reclosing after three-pole tripping
Fast measuring of voltage difference U
Diff
of the phase angle difference ϕ
Diff
and fre-
quency difference f
Diff
Alternatively, check of the de-energized state before reclosing
Closing at asynchronous system conditions with prediction of the synchronization
time
Settable minimum and maximum voltage