1.3 Characteristics
31
7SD5 Manual
C53000-G1176-C169-1
Verification of the synchronous conditions or de-energized state also possible
before the manual closing of the circuit breaker, with separate limit values
Also measurement via transformer
Measuring voltages optionally phase-phase or phase-earth
Voltage Protection
(optional)
Two overvoltage stages for the phase-earth voltages
Two overvoltage stages for the phase-phase voltages
Two overvoltage stages for the positive sequence voltage, optionally with com-
pounding
Two overvoltage stages for the negative sequence voltage
Two overvoltage stages for the zero sequence voltage or any other single-phase
voltage
Settable dropout to pickup ratios for the overvoltage protection functions
Two undervoltage stages for the phase-earth voltages
Two undervoltage stages for the phase-phase voltages
Two undervoltage stages for the negative sequence voltage;
Settable current criterion for undervoltage protection functions
Frequency
Protection
(optional)
Monitoring for underfrequency (f<) and/or overfrequency (f>) with 4 frequency limits
and delay times that are independently adjustable
Particularly insensitive to harmonics and abrupt phase angle changes
Large frequency range (approx. 25 Hz to 70 Hz)
Fault Locator Optionally single-ended (conventional) or double-ended fault location via communi-
cation interfaces
Initiated by trip command or reset of the fault detection
Fault location output in Ohm, kilometers or miles and % of line length
Output of the fault location also possible in BCD code
Parallel line compensation can be selected
Taking into consideration the load current in case of single-phase earth faults fed
from both sides (configurable)
Possibility to take into account line asymmetry and of different line sections
Circuit Breaker
Failure Protection
With definite time current stages for monitoring current flow through every pole of
the circuit breaker
With definite time monitoring time steps for single-pole and three-pole tripping
Start by trip command of every internal protection function
Start by external trip functions possible
Single-stage or two-stage
Short dropout and overshoot times
End fault protection and pole discrepancy monitoring possible