1 Introduction
32
7SD5 Manual
C53000-G1176-C169-1
Thermal Overload
Protection
Provides thermal replica of the current heat losses of the protected object
R.m.s. measurement of all three phase currents
Adjustable thermal and current-dependent warning stages
User-defined
Functions
Freely programmable combination of internal and external signals for the imple-
mentation of user-defined logic functions
All common logic functions
Time delays and set point interrogation
Commissioning,
Operation,
Maintenance
Display of magnitude and phase angle of local and remote measured values
Indication of the calculated differential and restraint currents
Display of the measured values of the communication link, such as transmission
delay and availability;
Function logout of a device from the line protection system during maintenance
work at an end of a power line, test mode and commissioning mode supported
Command
Processing
Switchgear can be switched on and off manually via local control keys, the program-
mable function keys on the front panel, via the system interface (e.g. by SICAM
®
or
LSA), or via the operator interface (using a personal computer and the operating
software DIGSI
®
);
Feedback on switching states via the circuit breaker auxiliary contacts (for com-
mands with feedback)
Plausibility monitoring of the circuit breaker position and monitoring of interlocking
conditions for switching operations
Monitoring
Functions
Increase of the availability of the device by monitoring of the internal measurement
circuits, auxiliary power supply, hardware, and software;
Current transformer and voltage transformer secondary circuits are monitored
using summation and symmetry check techniques
Monitoring of communication with statistics showing the availability of transmission
telegrams
Check of the consistency of protection settings at all line ends: blocking of the dif-
ferential protection system in case of inconsistent settings which could lead to a
malfunction
Trip circuit supervision possible
Check of local and remote measured values and comparison of both
Broken wire supervision for the secondary CT circuits with fast phase segregated
blocking of the line protection system in order to avoid malfunction
Supervision of measuring voltage failure using "Fuse Failure Monitor"
Ancillary Functions Battery buffered real-time clock, which may be synchronized via a synchronization
signal (e.g. DCF77, IRIG B, GPS via satellite receiver), binary input or system inter-
face
Automatic time synchronization between the devices at the ends of the protected
object via the protection data transmission
www . ElectricalPartManuals . com