EasyManua.ls Logo

Siemens siprotec 7SD5

Siemens siprotec 7SD5
698 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.1 Mounting and Connections
461
7SD5 Manual
C53000-G1176-C169-1
The set nominal current of the current input transformers are checked on the input/out-
put board C-I/O-2. All jumpers must be set for one nominal current, i.e. one jumper
(X61 to X64) for each input transformer and additionally the common jumper X60. But:
In the version with sensitive earth fault current input (input transformer T8) there is no
jumper X64.
Jumpers X71, X72 and X73 on the input/output board C-I/O-2 are used to set the bus
address and must not be changed. The following table lists the jumper presettings.
Mounting location:
with housing size
1
/
2
: No. 3 in Figure 3-3, slot 33,
with housing size
1
/
1
: No. 3 in Figure 3-4, slot 33 right.
Table 3-9 Jumper settings of Board Address of the input/output board C-I/O-2
Jumper Factory Setting
X71 1-2 (H)
X72 1-2 (H)
X73 2-3 (L)
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens siprotec 7SD5

Related product manuals