EasyManua.ls Logo

Siemens siprotec 7SD5

Siemens siprotec 7SD5
698 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.23 User Defined Functions (CFC)
573
7SD5 Manual
C53000-G1176-C169-1
Maximum Number of TICKS in the Task Levels
1)
When the sum of TICKS of all blocks exceeds the limits before-mentioned, an error message is output by CFC.
Processing Times in TICKS required by the Individual Elements
Task Level Limit in TICKS
1)
MW_BEARB (Measured Value Processing) 10 000
PLC1_BEARB (Slow PLC Processing) 1 900
PLC_BEARB (Fast PLC Processing) 200
SFS_BEARB (switchgear interlocking) 10 000
Individual Element Number of TICKS
Block, basic requirement 5
Each input more than 3 inputs for generic modules 1
Connection to an input signal 6
Connection to an output signal 7
Additional for each chart 1
Operating sequence module CMD_CHAIN 34
Flipflop D_FF_MEMO 6
Loop module LOOP 8
Decoder DM_DECODE 8
Dynamic OR DYN_OR 6
Addition ADD 26
Subtraction SUB 26
Multiplication MUL 26
Division DIV 54
Square root SQUARE_ROOT 83
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens siprotec 7SD5

Related product manuals