EasyManuals Logo

Siemens siprotec 7SD5 User Manual

Siemens siprotec 7SD5
698 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #640 background imageLoading...
Page #640 background image
A Appendix
640
7SD5 Manual
C53000-G1176-C169-1
5 >Reset LED (>Reset LED) Device SP * * * LED BI BO
7 >Setting Group Select Bit 0 (>Set
Group Bit0)
Change Group SP * * * LED BI BO
8 >Setting Group Select Bit 1 (>Set
Group Bit1)
Change Group SP * * * LED BI BO
11 >User defined annunciation 1
(>Annunc. 1)
Device SP * * * * LED BI BO 192 27 1 Yes
12 >User defined annunciation 2
(>Annunc. 2)
Device SP * * * * LED BI BO 192 28 1 Yes
13 >User defined annunciation 3
(>Annunc. 3)
Device SP * * * * LED BI BO 192 29 1 Yes
14 >User defined annunciation 4
(>Annunc. 4)
Device SP * * * * LED BI BO 192 30 1 Yes
15 >Test mode (>Test mode) Device SP ON
OFF
* * LED BI BO 135 53 1 Yes
16 >Stop data transmission
(>DataStop)
Device SP * * * LED BI BO 135 54 1 Yes
51 Device is Operational and Pro-
tecting (Device OK)
Device OUT ON
OFF
* * LED BO 135 81 1 Yes
52 At Least 1 Protection Funct. is
Active (ProtActive)
Device IntSP ON
OFF
* * LED BO 192 18 1 Yes
55 Reset Device (Reset Device) Device OUT * * * LED BO 192 4 1 No
56 Initial Start of Device (Initial Start) Device OUT ON * * LED BO 192 5 1 No
60 Reset LED (Reset LED) Device OUT_
Ev
ON * * LED BO 192 19 1 No
67 Resume (Resume) Device OUT ON * * LED BO 135 97 1 No
68 Clock Synchronization Error
(Clock SyncError)
Device OUT ON
OFF
**LEDBO
69 Daylight Saving Time (DayLight-
SavTime)
Device OUT ON
OFF
**LEDBO
70 Setting calculation is running
(Settings Calc.)
Device OUT ON
OFF
* * LED BO 192 22 1 Yes
71 Settings Check (Settings Check) Device OUT * * * LED BO
72 Level-2 change (Level-2 change) Device OUT ON
OFF
**LEDBO
73 Local setting change (Local
change)
Device OUT * *
110 Event lost (Event Lost) Device OUT_
Ev
ON * * LED BO 135 130 1 No
113 Flag Lost (Flag Lost) Device OUT ON * m LED BO 135 136 1 Yes
125 Chatter ON (Chatter ON) Device OUT ON
OFF
* * LED BO 135 145 1 Yes
126 Protection ON/OFF (via system
port) (ProtON/OFF)
Device IntSP ON
OFF
**LEDBO
127 Auto Reclose ON/OFF (via
system port) (AR ON/OFF)
Auto Reclose IntSP ON
OFF
**LEDBO
128 Teleprot. ON/OFF (via system
port) (TelepONoff)
Device IntSP ON
OFF
**LEDBO
140 Error with a summary alarm
(Error Sum Alarm)
Device OUT ON
OFF
* * LED BO 192 47 1 Yes
144 Error 5V (Error 5V) Device OUT ON
OFF
* * LED BO 135 164 1 Yes
160 Alarm Summary Event (Alarm
Sum Event)
Device OUT * * * LED BO 192 46 1 Yes
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens siprotec 7SD5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SD5 and is the answer not in the manual?

Siemens siprotec 7SD5 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SD5
CategoryRelays
LanguageEnglish

Related product manuals