A.8 Information List
641
7SD5 Manual
C53000-G1176-C169-1
161 Failure: General Current Supervi-
sion (Fail I Superv.)
Measurem.Superv OUT * * * LED BO 192 32 1 Yes
163 Failure: Current Balance (Fail I
balance)
Measurem.Superv OUT ON
OFF
* * LED BO 135 183 1 Yes
164 Failure: General Voltage Supervi-
sion (Fail U Superv.)
Measurem.Superv OUT * * * LED BO 192 33 1 Yes
165 Failure: Voltage summation
Phase-Earth (Fail Σ U Ph-E)
Measurem.Superv OUT ON
OFF
* * LED BO 135 184 1 Yes
167 Failure: Voltage Balance (Fail U
balance)
Measurem.Superv OUT ON
OFF
* * LED BO 135 186 1 Yes
168 Failure: Voltage absent (Fail U
absent)
Measurem.Superv OUT ON
OFF
* * LED BO 135 187 1 Yes
169 VT Fuse Failure (alarm >10s) (VT
FuseFail>10s)
Measurem.Superv OUT ON
OFF
* * LED BO 135 188 1 Yes
170 VT Fuse Failure (alarm instanta-
neous) (VT FuseFail)
Measurem.Superv OUT ON
OFF
**LEDBO
171 Failure: Phase Sequence (Fail
Ph. Seq.)
Measurem.Superv OUT ON
OFF
* * LED BO 192 35 1 Yes
177 Failure: Battery empty (Fail Bat-
tery)
Device OUT ON
OFF
* * LED BO 135 193 1 Yes
181 Error: A/D converter (Error A/D-
conv.)
Device OUT ON
OFF
* * LED BO 135 178 1 Yes
182 Alarm: Real Time Clock (Alarm
Clock)
Device OUT
183 Error Board 1 (Error Board 1) Device OUT ON
OFF
* * LED BO 135 171 1 Yes
184 Error Board 2 (Error Board 2) Device OUT ON
OFF
* * LED BO 135 172 1 Yes
185 Error Board 3 (Error Board 3) Device OUT ON
OFF
* * LED BO 135 173 1 Yes
186 Error Board 4 (Error Board 4) Device OUT ON
OFF
* * LED BO 135 174 1 Yes
187 Error Board 5 (Error Board 5) Device OUT ON
OFF
* * LED BO 135 175 1 Yes
188 Error Board 6 (Error Board 6) Device OUT ON
OFF
* * LED BO 135 176 1 Yes
189 Error Board 7 (Error Board 7) Device OUT ON
OFF
* * LED BO 135 177 1 Yes
190 Error Board 0 (Error Board 0) Device OUT ON
OFF
* * LED BO 135 210 1 Yes
191 Error: Offset (Error Offset) Device OUT ON
OFF
**LEDBO
192 Error:1A/5Ajumper different from
setting (Error1A/5Awrong)
Device OUT ON
OFF
* * LED BO 135 169 1 Yes
193 Alarm: Analog input adjustment
invalid (Alarm adjustm.)
Device OUT ON
OFF
* * LED BO 135 181 1 Yes
194 Error: Neutral CT different from
MLFB (Error neutralCT)
Device OUT ON
OFF
* * LED BO 135 180 1 Yes
196 Fuse Fail Monitor is switched
OFF (Fuse Fail M.OFF)
Measurem.Superv OUT * * LED BO 135 196 1 Yes
197 Measurement Supervision is
switched OFF (MeasSup OFF)
Measurem.Superv OUT ON
OFF
* * LED BO 135 197 1 Yes
203 Waveform data deleted (Wave.
deleted)
Osc. Fault Rec. OUT_
Ev
ON * * LED BO 135 203 1 No
273 Set Point Phase L1 dmd> (SP.
IL1 dmd>)
Set Points(MV) OUT on
off
**LEDBO
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation