A.8 Information List
643
7SD5 Manual
C53000-G1176-C169-1
380 >CB aux. contact 3pole Open
(>CB 3p Open)
P.System Data 2 SP * * * LED BI BO 150 79 1 Yes
381 >Single-phase trip permitted from
ext.AR (>1p Trip Perm)
P.System Data 2 SP ON
OFF
**LEDBIBO
382 >External AR programmed for
1phase only (>Only 1ph AR)
P.System Data 2 SP ON
OFF
**LEDBIBO
383 >Enable all AR Zones / Stages
(>Enable ARzones)
P.System Data 2 SP ON
OFF
ON
OFF
* LED BI BO
385 >Lockout SET (>Lockout SET) P.System Data 2 SP ON
OFF
* * LED BI BO 150 35 1 Yes
386 >Lockout RESET (>Lockout
RESET)
P.System Data 2 SP ON
OFF
* * LED BI BO 150 36 1 Yes
395 >I MIN/MAX Buffer Reset (>I
MinMax Reset)
Min/Max meter SP ON * * LED BI BO
396 >I1 MIN/MAX Buffer Reset (>I1
MiMaReset)
Min/Max meter SP ON * * LED BI BO
397 >U MIN/MAX Buffer Reset (>U
MiMaReset)
Min/Max meter SP ON * * LED BI BO
398 >Uphph MIN/MAX Buffer Reset
(>UphphMiMaRes)
Min/Max meter SP ON * * LED BI BO
399 >U1 MIN/MAX Buffer Reset (>U1
MiMa Reset)
Min/Max meter SP ON * * LED BI BO
400 >P MIN/MAX Buffer Reset (>P
MiMa Reset)
Min/Max meter SP ON * * LED BI BO
401 >S MIN/MAX Buffer Reset (>S
MiMa Reset)
Min/Max meter SP ON * * LED BI BO
402 >Q MIN/MAX Buffer Reset (>Q
MiMa Reset)
Min/Max meter SP ON * * LED BI BO
403 >Idmd MIN/MAX Buffer Reset
(>Idmd MiMaReset)
Min/Max meter SP ON * * LED BI BO
404 >Pdmd MIN/MAX Buffer Reset
(>Pdmd MiMaReset)
Min/Max meter SP ON * * LED BI BO
405 >Qdmd MIN/MAX Buffer Reset
(>Qdmd MiMaReset)
Min/Max meter SP ON * * LED BI BO
406 >Sdmd MIN/MAX Buffer Reset
(>Sdmd MiMaReset)
Min/Max meter SP ON * * LED BI BO
407 >Frq. MIN/MAX Buffer Reset
(>Frq MiMa Reset)
Min/Max meter SP ON * * LED BI BO
408 >Power Factor MIN/MAX Buffer
Reset (>PF MiMaReset)
Min/Max meter SP ON * * LED BI BO
410 >CB1 aux. 3p Closed (for AR,
CB-Test) (>CB1 3p Closed)
P.System Data 2 SP * * * LED BI BO 150 80 1 Yes
411 >CB1 aux. 3p Open (for AR, CB-
Test) (>CB1 3p Open)
P.System Data 2 SP * * * LED BI BO 150 81 1 Yes
501 Relay PICKUP (Relay PICKUP) P.System Data 2 OUT * * M LED BO 192 84 2 Yes
502 Relay Drop Out (Relay Drop Out) P.System Data 2 OUT
503 Relay PICKUP Phase L1 (Relay
PICKUP L1)
P.System Data 2 OUT * * m LED BO 192 64 2 Yes
504 Relay PICKUP Phase L2 (Relay
PICKUP L2)
P.System Data 2 OUT * * m LED BO 192 65 2 Yes
505 Relay PICKUP Phase L3 (Relay
PICKUP L3)
P.System Data 2 OUT * * m LED BO 192 66 2 Yes
506 Relay PICKUP Earth (Relay
PICKUP E)
P.System Data 2 OUT * * m LED BO 192 67 2 Yes
507 Relay TRIP command Phase L1
(Relay TRIP L1)
P.System Data 2 OUT * * m LED BO 192 69 2 No
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens siprotec 7SD5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SD5 and is the answer not in the manual?

Siemens siprotec 7SD5 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SD5
CategoryRelays
LanguageEnglish

Related product manuals