2 Functions
148
7UM61 Manual
C53000-G1176-C127-3
2.24.3 Settings
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
2.24.4 Information List
Addr. Parameter C Setting Options Default Setting Comments
6501 STARTUP MOTOR OFF
ON
Block relay
OFF Motor Starting Time Su-
pervision
6502 START. CURRENT 1A 0.10 .. 16.00 A 3.12 A Starting Current of Motor
5A 0.50 .. 80.00 A 15.60 A
6503 STARTING TIME 1.0 .. 180.0 sec 8.5 sec Starting Time of Motor
6504 LOCK ROTOR TIME 0.5 .. 120.0 sec; 6.0 sec Permissible Locked Rotor
Time
6505 I MOTOR START 1A 0.60 .. 10.00 A 1.60 A Current Pickup Value of
Motor Starting
5A 3.00 .. 50.00 A 8.00 A
No. Information Type of In-
formation
Comments
6801 >BLK START-SUP EM >BLOCK Motor Starting Supervision
6805 >Rotor locked EM >Rotor is locked
6811 START-SUP OFF AM Starting time supervision switched OFF
6812 START-SUP BLK AM Starting time supervision is BLOCKED
6813 START-SUP ACT AM Starting time supervision is ACTIVE
6821 START-SUP TRIP AM Starting time supervision TRIP
6822 Rotor locked AM Rotor is LOCKED after Locked Rotor Time
6823 START-SUP PU AM Starting time supervision picked up