2 Functions
38
7UM61 Manual
C53000-G1176-C127-3
2.3.3 Information List
273 STAR-POINT low-resist.
high-resist.
high-resist. Earthing of Machine Star-
point
274A ATEX100 YES
NO
NO Storage of th. Replicas w/o
Power Supply
276 TEMP. UNIT Celsius
Fahrenheit
Celsius Unit of temperature mea-
surement
280 TMin TRIP CMD 0.01 .. 32.00 sec 0.15 sec Minimum TRIP Command
Duration
281 BkrClosed I MIN 1A 0.04 .. 1.00 A 0.04 A Closed Breaker Min.
Current Threshold
5A 0.20 .. 5.00 A 0.20 A
No. Information Type of In-
formation
Comments
361 >FAIL:Feeder VT EM >Failure: Feeder VT (MCB tripped)
5002 Operat. Cond. AM Suitable measured quantities present
5145 >Reverse Rot. EM >Reverse Phase Rotation
5147 Rotation L1L2L3 AM Phase Rotation L1L2L3
5148 Rotation L1L3L2 AM Phase Rotation L1L3L2
Addr. Parameter C Setting Options Default Setting Comments